Mechanical
Gas services design
Natural gas and LPG installation design — supply capacity, pipe sizing, ventilation and the safety requirements of IGEM standards.
- Discipline
- Mechanical
- Typical timescale
- 1 to 2 weeks alongside the mechanical design
WHAT IT IS
Gas services design covers the route from the meter to the appliance: incoming supply and meter capacity, pipe sizing and materials, ventilation and flueing of the plant room, and the safety provisions — isolation, detection, purge — that the installation is required to have.
The design work is governed by the IGEM technical standards rather than by a single British Standard, and by the Gas Safety (Installation and Use) Regulations 1998. Installation and commissioning must be carried out by a Gas Safe registered engineer; design sets what that engineer installs.
WHEN YOU NEED IT
Where a building has a gas-fired appliance of any size — boilers, direct-fired heaters, commercial catering, laboratory or process gas — and on any project where the existing supply or meter may not have the capacity for a changed load.
Also on the way out: Scotland's New Build Heat Standard prohibits direct emissions heating in new buildings applying for a warrant from 1 April 2024, so on a new build in Scotland the honest answer is often that gas is not available for heating, and the design work becomes the electrification route instead.
OUR PROCESS
Load first, then the supply. The connected load and the diversity applied to it determine whether the existing meter and service will do, and a capacity application to the gas transporter has a lead time that needs to start early rather than at tender.
Plant room ventilation and flue routing are resolved with the architect at coordination stage, because both need builder's work and both are difficult to add later.
DELIVERABLES
What you receive
- Connected load and diversity calculation
- Supply and meter capacity assessment
- Gas pipe sizing calculations
- Gas services layouts and schematics
- Plant room ventilation and flue design
- Isolation, detection and interlock requirements
STANDARDS
Standards applied
The editions in force at the time of design. Where a standard is amended mid-project we confirm which edition the appointment is based on.
- Gas Safety (Installation and Use) Regulations 1998as amendedlegislation.gov.uk
- IGEM/UP/1Strength and tightness testing and direct purging of industrial and commercial gas installationsIGEM
- IGEM/UP/2Installation pipework on industrial and commercial premisesIGEM
- IGEM/UP/10Installation of flued gas appliances in industrial and commercial premisesIGEM
- BS 6644:2011+A1:2016Specification for the installation and maintenance of gas-fired hot water boilers of rated inputs between 70 kW and 1.8 MWBSI
- BS 6891:2015+A1:2019Specification for the installation and maintenance of low pressure gas installation pipework of up to 35 mm in domestic premisesBSI
- New Build Heat StandardDirect emissions heating in new buildings, ScotlandScottish Government
QUESTIONS
Common questions
Can a new building in Scotland still be heated by gas?
Not as its heating system. The New Build Heat Standard, in Section 6 of the Scottish Technical Handbooks, prohibits direct emissions heating systems in new buildings whose building warrant was applied for on or after 1 April 2024. Gas may still serve other uses, such as commercial catering, and existing buildings are not affected.
Who can install a commercial gas installation?
A Gas Safe registered engineer holding the relevant commercial competencies for the appliance type and pipework size. Design is a separate activity from installation: the design defines pipe sizes, materials, ventilation and safety provisions, and the registered installer is responsible for installing, testing, purging and commissioning to IGEM/UP/1.
How is gas pipe sizing calculated?
From the connected load of each appliance with diversity applied, the pressure available at the meter outlet, and the permitted pressure drop across the installation — 1 mbar for natural gas installations under BS 6891 in domestic premises, and to the pressure regime set by IGEM/UP/2 on commercial installations. Sizing is calculated leg by leg, not estimated from the meter size.